EMV

Valves & Accessories

EMV series mechanically actuated seismic valves are designed for use in gas networks and industrial pipelines, especially in earthquake prone areas. The valve cuts off the line when any seismic activity is detected and helps prevent hazardous situations.

EMV
Safety

EMV offers safety in earthquake prone areas and can help prevent gas leakages

EMV
Media

Can be used with noncorrosive gases such as PNG , LPG, Town Gas, Air, etc.

EMV
Easy Installation

With its inline & compact design, EMV valves can be easily mounted on the gas line

Description

ESKA EMV Series Earthquake Valve is a shut-off valve which is activated during seismic oscillation. Activation and non-activation waves are defined in TS 12884 Turkish Standard. This Turkish standard was created based on ANSI Z11 standard in United States.

Once mechanical actuation system senses any seismic oscillation, valve shuts the gas off and needs to be rearmed manually in order to reactivate gas flow. This valve basically is a manual reset, normally open gas valve. Main aim is  to decrease the risk of gas leakage related fire, when earthquake occurs. In countries this safety system is available, main regulation is done by fire safety department.

Technical Specifications

MediumNon‐corrosive gases such as Natural Gas (Methane), LPG, Town Gas, Air, etc…
Connection or Port Size1”, 11/4”, 11/2”, 2” Threaded (Female) and DN65, DN80 ,DN100 Flanged
Positionnormally open
Montage positionVertical
Maximum working pressure0,5 bar
Ambient Temperature‐23°C up to 51,5°C
Resetmanually
Material StandardAluminum-EN 1706 /Brass EN12164 and EN12165 /Rubber-EN 549